HXGT6 SF6 RMU...
SF6 Ring Main Unit Switchgear Type HXGT6(XGN58)-12
-1.gif)
Product Features:
a. Ring main unit is composed of three compartments. The load switch is laid in the sealed cubicle welded by stainless steel plate. There is SF6 gas of 0.04Mpa as the medium of extinction and insulation.
b. There are three positions, namely closing, isolating, earthing separately, whose positions are determined by the indicator on the mechanism panel.
c. The cable incoming/outgoing line uses cable connector (plug ins).
d. There is a separate operation mechanism in each compartment, where you can realize manual operation and manual and motor operation. There is closing/opening indication on the operation panel.
e. The fuse is installed in the epoxy resin tube in the middle of the cubicle. Due to the needle type mechanism of fuse and the opening device of operation mechanism in load switch are connected together, once the fuse is blew out with fault, the tripping mechanism will make the load switch opening.
f. The load switch applies revolving extinction arc principle, which will make contact long life endurance.
g. There is manometer in the front of the switchgear to monitor the pressure of the SF6 gas.
h. In order to prevent the inner of equipment from hyperbaric with circuit fault, there is a pressure release device at the bottom of the switchgear.
-2.gif)
e :
Ordering notic:
Please provide the following data :
a. Name, specification, type, quantity, delivery date of product, rated voltage of fuse ;
b. Pareto diagrams and layout plan of RMU ;
c. Spare parts needed, such as charging/discharging device ;
d. cubicle colour;
e. Any special request can be settled by negotiation.